Introduction

  • Codes and Standards
  • Features and Benefits
  • MasterPact NW Circuit Breaker Design
  • MasterPact NW Cradle Design
  • MasterPact NW with ArcBlock<span><span><span style="font-family: Arial; ">™</span></span></span> Technology
  • MasterPact NT Circuit Breaker and Cradle Design
  • Correction Factors
  • Shipping Weights
  • MasterPact Circuit Breakers with MicroLogic Trip Units
  • Power Meter Functions
  • Display Function
  • Instantaneous RMS Measurements
  • Maximum / Minimum Ammeter
  • Energy Metering
  • Demand and Maximum Demand Values
  • Power Quality
  • Contact Wear
  • Circuit Breaker Load Profile
  • Management of Installed Devices
  • Display of MicroLogic Trip Unit Measurements and Alarms
  • Status Indications and Remote Control
  • Main Characteristics
  • Communication Components and FDM121 Connections
  • Display of MicroLogic Trip Unit Measurements and Trips
  • Status Indications
  • Remote Control
  • Communication Components and FDM128 Connections

Thermal Imaging

Ammeter (a) trip unit without 24 vdc power supply at f1 and f2, ammeter (a) trip unit with 24 vdc power supply at f1 and f2, power (p) and harmonic (h) trip unit without 24 vdc power supply at f1 and f2, power (p) and harmonic (h) trip unit with 24 vdc power supply at f1 and f2, true rms current sensing, protection settings, ammeter measurements, communication network, configuring alarms and other protection functions, maintenance record, load shedding and reconnection parameters, indication option via programmable contacts, trip and alarm histories, waveform capture, customized alarm programming, additional technical characteristics for type p and type h trip units.

Long-Time Trip Functions

Short-Time Trip Functions

Instantaneous trip function.

Ground-Fault Trip Functions

Wiring System ULP

Four functional levels, modbus principle, ethernet principle, com option in masterpact circuit breakers, ife interface, ife interface + gateway description, 24 vdc power supply, required circuit breaker communication modules, characteristics, technical characteristics, simplified ifm installation, description, io (input/output) application module for low-voltage circuit breaker resources, pre-defined application, user-defined applications, application rotary switch, setting locking pad, compatible devices (configuration and device management).

  • Options for Remote Operation
  • Spring-Charging Motor (MCH)
  • Shunt Trip (MX1) and Shunt Close (XF)
  • Additional Shunt Trip (MX2) or Undervoltage Trip (MN)
  • Time-Delay Module for Undervoltage Trip
  • Ready-to-Close Switch (PF)
  • Electrical Closing Push Button (BPFE)
  • Remote Reset (RES) and Automatic Reset After Fault Trip
  • Auxiliary Switch (OF)
  • Overcurrent Trip Switch (SDE)
  • Connected Closed Switch (EF)
  • Cradle Position Switch
  • External Neutral Current Transformer (CT)
  • External Sensor for Source Ground-Return (SGR) and Modified Differential Ground-Fault (MDGF) Protection
  • Metering Current Transformers (CTs)
  • Voltage Measurement Inputs
  • Sensor Plugs
  • Adjustable Rating Plugs
  • External Power Supply Module
  • External Battery Backup Module
  • M2C/M6C Programmable Contact Modules
  • Zone-Selective Interlocking (ZSI)
  • Restraint Interface Module (RIM)
  • Cradle Connections
  • Hand-Held Test Kit
  • Full-Function Test Kit
  • Lockable Push Button Cover
  • Open Position Padlock and Key Lock Provisions
  • Disconnected Position Locking
  • Door Interlock (VPEC)
  • Racking Interlock Between Racking Handle and Off Position (IBPO)
  • Cable Door Interlock Kit
  • Source Changeover Interlocks
  • Open Door Racking Interlock (VPOC)
  • Automatic Spring Discharge Mechanism (DAE)
  • Cradle Rejection Kits
  • Rail Padlocking
  • Mechanical Operation Counter (CDM)
  • Shutter and Shutter Lock
  • Door Escutcheon (CDP)
  • Transparent Cover (CCP) for Door Escutcheon
  • MasterPact NW Remote Racking Device
  • Wiring Diagrams for MasterPact NW Circuit Breakers
  • Wiring Diagrams for MasterPact NT Circuit Breakers
  • Additional Wiring Information for MasterPact NW NT Circuit Breakers
  • MasterPact NT Enclosure Information
  • UL<span><span><span style="font-family: Arial; "> ® </span></span></span> and ANSI Three-Pole Drawout Circuit Breakers
  • UL and ANSI Three-Pole Fixed Circuit Breakers
  • UL and ANSI Four-Pole Drawout Circuit Breakers
  • UL and ANSI Four-Pole Fixed Circuit Breakers
  • IEC Three-Pole Drawout Circuit Breakers
  • IEC Three-Pole Fixed Circuit Breakers
  • IEC Four-Pole Drawout Circuit Breakers
  • IEC Four-Pole Fixed Circuit Breakers
  • Neutral Current Transformers
  • Enclosure Information
  • UL<span><span><span style="font-family: Arial; "> ® </span></span></span>/ANSI Three-Pole Drawout Circuit Breakers
  • UL/ANSI Three-Pole Fixed Circuit Breakers
  • UL/ANSI Four-Pole Drawout Circuit Breakers
  • UL/ANSI Four-Pole Fixed Circuit Breakers
  • Accessory Dimensions
  • Overview of Selection Procedure
  • T-Frame Circuit Breaker Selection
  • T-Frame Switch Selection
  • W-Frame Circuit Breaker Selection
  • W-Frame Switch Selection
  • Y-Frame Circuit Breaker Selection
  • Y-Frame Switch Selection
  • MicroLogic 6.0 A/P/H Trip Units
  • MicroLogic 5.0/6.0 A/P/H Trip Unit
  • MicroLogic 3.0 Trip Units
  • MicroLogic 2.0A Trip Unit
  • Instantaneous Override Values No. 613.10
  • MasterPact NW/NT Low Arc Flash Circuit Breakers

For the best experience of this site, please enable Javascript for the www.productinfo.schneider-electric.com domain.

MicroLogic ™ Electronic Trip Systems

Overview of micrologic trip systems, p trip unit with power metering.

an electronic trip unit

All MasterPact circuit breakers are equipped with the MicroLogic trip system to protect power circuits and loads. MicroLogic trip systems use a set of current transformers (called CTs or sensors) to sense current, a trip unit to evaluate the current, and a tripping solenoid to trip the circuit breaker. Adjustable rotary switches on the trip unit allow the user to set the proper overcurrent or equipment ground-fault current protection required in the electrical system. If current exceeds a set value for longer than its set time delay, the trip system opens the circuit breaker. Alarms may be programmed for remote indications. Measurements of current, voltage, frequency, power, and power quality optimize continuity of service and energy management. MicroLogic trip units can be changed on-site.

Integration of protection functions in the Application Specific Integrated Circuit (ASIC) electronic component used in all MicroLogic trip units guarantees a high degree of reliability and immunity to conducted or radiated disturbances. On MicroLogic P and H trip units, advanced functions are managed by an independent microprocessor.

MasterPact circuit breakers are shipped with the long-time pickup switch set at 1.0 and all other trip unit adjustments set at their lowest settings. Actual settings required for a specific application must be determined by a qualified consultant or plant engineer. A coordination study is recommended to provide coordination between all circuit breakers in the distribution system.

The thermal imaging function protects the cables or bus bars from overheating in case of low amplitude repetitive faults. Such overheating can be due to repetitive motor starting, fluctuating load, intermittent ground faults, or subsequent closing after a fault.

Traditional electronic protection does not protect against repetitive faults because the duration of each overload above the pickup setting is too short to achieve effective tripping. Nevertheless, each overload involves a temperature rise in the installation, the cumulative effect of which could lead to overheating of the system.

The thermal imaging function remembers and integrates the thermal heating caused by each pickup setting overrun. Before tripping, the integrated heating value will reduce the associated time delay and, therefore, the reaction of the trip unit will be closer to the real heating of the power network system.

After tripping, the function will also reduce the time delay when closing the circuit breaker on an overload.

Power Supply Information

Provides fault protection for LSIG functions.

Provides LED trip indication (powered by an onboard battery).

All display functions and trip unit features power-up with current flow on one phase greater than or equal to the values in the table to the left.

Ground-fault push-to-trip button works for testing ground fault with current flow on one phase greater than or equal to the values shown in the following table.

The Ammeter (A) trip unit provides all of the above plus additional functionality when powered by external 24 Vdc power supply:

Ammeter and bar graph displays are functional with or without current flowing through the circuit breaker.

Trip settings and (Max) current readings can be accessed on the display by pressing navigation button with or without current flowing through the circuit breaker.

The ground-fault push-to-trip button works for testing ground fault with or without current flowing through the circuit breaker.

Optional Modbus™ communications—also requires a separate 24 Vdc power supply for the circuit breaker communications module.

The P and H trip units were designed to be used with the external 24 Vdc power supply. The large LCD display requires too much current to be powered by current flow through the circuit breaker. The P and H trip units do have a voltage power supply which will power the trip unit with 100 Vac or more between two phases or phase to neutral. The standard configuration for the voltage probes inside the circuit breaker is at the bottom connections. If the circuit breaker was open in a top fed application, there would be no voltage at the bottom of the circuit breaker and the trip unit would not be powered.

Provides all of the above.

LCD display and backlight are functional.

Ground-fault push-to-trip button works for testing ground fault.

All metering, monitoring, and history logs are functional.

Communications from trip unit to M2C and M6C programmable contact modules are powered by a 24 Vdc supply at F1 and F2. M6C also requires a 24 Vdc external power supply.

Modbus communications—also requires a separate 24 Vdc power supply for the circuit breaker communications module.

MicroLogic Trip Units — Overview

The sensing system responds to the flow of current through the circuit breaker. Electronic trip circuit breakers are limited to ac systems because the electronic trip system uses current transformers to sense the current. The MicroLogic trip unit samples the current waveform to provide true RMS protection through the 15th harmonic.

This true RMS sensing gives accurate values for the magnitude of a non-sinusoidal waveform. Therefore, the heating effects of harmonically distorted waveforms are accurately evaluated.

The MicroLogic H trip unit provides additional sampling of the waveforms to measure and provide waveform capture of harmonic distortion to the 31st harmonic.

MasterPact universal power circuit breakers use MicroLogic electronic trip systems to sense overcurrents and trip the circuit breaker. The MicroLogic basic trip unit is standard and all MasterPact circuit breakers can be equipped with the optional MicroLogic trip systems listed below:

MicroLogic Basic Trip Unit (standard).

— 2.0 basic protection (LS0, IEC)

— 3.0 basic protection (LI, UL ® /ANSI)

— 5.0 selective protection (LSI)

MicroLogic A: Trip Unit with Ammeter.

— 2.0A basic protection (LS0, IEC)

— 3.0A basic protection (LI, UL/ANSI)

— 5.0A selective protection (LSI)

— 6.0A selective protection with ground-fault protection for equipment (LSIG)

MicroLogic P: Trip Unit with Power Metering.

— 5.0P selective protection (LSI)

— 6.0P selective protection with ground-fault protection for equipment (LSIG)

MicroLogic H: Trip Unit with Harmonic Metering.

— 5.0H selective protection (LSI)

— 6.0H selective protection with ground-fault protection for equipment (LSIG)

MicroLogic Trip Unit Features

Micrologic 2.0, 3.0 and 5.0 basic trip units.

The MicroLogic 2.0, 3.0, and 5.0 trip units protect power circuits.

Protection thresholds and delays are set using the rotary switches.

A full-range of long-time settings are available via the field-installable adjustable rating plugs.

Overload protection

— True RMS long-time protection

— Thermal imaging: active thermal imaging before and after tripping

Short-circuit protection

— Short-time RMS

— Selection of I 2 t type (ON or OFF) for short-time delay

Instantaneous protection

Neutral protection on four-pole circuit breakers

MicroLogic 5.0 Basic Trip Unit

an electronic trip unit

MicroLogic 2.0 and 3.0 Basic Trip Unit Settings

an electronic trip unit

MicroLogic 5.0 Basic Trip Unit Settings

Micrologic 2.0a, 3.0a, 5.0a and 6.0a trip units with ammeter.

MicroLogic A trip units protect power circuits and provide current measurements, overload protection, and short-circuit protection. In addition, the 6.0A trip units also provide ground-fault protection for equipment.

Protection thresholds and delays are set using the rotary switches. The selected values are momentarily displayed in amperes and in seconds. A full-range of long-time settings are available via the field-installable rating plug.

Overload protection (true RMS long-time protection)

Thermal imaging (active thermal imaging before and after tripping)

— I 2 t ON or OFF for short-time delay

Ground-fault protection for equipment

— Residual ground-fault protection for equipment

— Source ground-return ground-fault protection for equipment

— Modified differential ground-fault protection (MDGF) for equipment

ZSI: Zone-selective interlocking

— A ZSI terminal block may be used to interconnect a number of trip units to provide total discrimination for short-time and equipment ground-fault protection, without delay for tripping

— Not available for 3.0 A trip unit

— Not available for 2.0 A trip unit if installed as upstream device

MicroLogic 6.0A Trip Unit

MicroLogic A trip units measure the true RMS value of currents. They provide continuous current measurement from 0.2 to 20 x I n with an accuracy of 1.5% (including sensors). No auxiliary source is needed where I > 0.2 x I n . The optional external power supply (24 Vdc) makes it possible to display currents where I < 0.2 x I n and to store values of the interrupted current. A digital LCD screen continuously displays the most heavily loaded phase (Imax) or displays the Ia, Ib, Ic, Ig, and (on four-pole circuit breakers only) In stored current and setting values by successively pressing the navigation button.

Four wire Modbus, RTU, RS485 or two wire Modbus, TRU, RS485 plus ULP. See Additional Wiring Information for MasterPact NW NT Circuit Breakers .

In conjunction with an optional communication network, the trip unit transmits the following parameters:

Setting values.

All ammeter measurements.

Tripping causes.

an electronic trip unit

MicroLogic 2.0A and 3.0A Trip Unit Settings

an electronic trip unit

MicroLogic 5.0A and 6.0A Trip Unit Settings

an electronic trip unit

MicroLogic 6.0A Trip Unit Ground-Fault Settings

Micrologic 5.0p and 6.0p trip units with power metering.

The adjustable protection functions of the 5.0P and 6.0P trip units are identical to those of MicroLogic A trip unit (overloads, short circuits, equipment ground-fault protection); see MicroLogic 2.0A, 3.0A, 5.0A and 6.0A Trip Units with Ammeter .

These units also feature:

Fine adjustment : Within the range below the rotary switch setting, fine adjustments of pickups/delays in steps of 1 A/s (except for short-time and ground-fault) are possible on the keypad or remotely by the communication network.

Inverse definite minimum time lag (IDMTL) setting : Coordination with fuse-type or medium-voltage protection systems is optimized by adjusting the long-time delay curve around 6 x I r axis. This setting ensures better coordination with certain loads.

Neutral protection : On three-pole circuit breakers, neutral protection may be set using the keypad or remotely using the communication network to one of four positions:

— 1/2N (1/2 x I n )

— 1N (1 x I n )

— 2N (2 x I n )

MicroLogic 6.0P Trip Unit

When the cover is closed, the keypad may no longer be used to change the protection settings, but it still provides access to the displays for measurements, histories, indicators, etc. Depending on the thresholds and time delays set, the MicroLogic P trip unit monitors current, voltage, power, frequency, and phase sequence. Each threshold overrun may be signalled remotely via the communication network.

Each threshold overrun may be combined with tripping (protection) or an indication carried out by an optional M2C/M6C programmable contact (alarm), or both (protection and alarm).

The maintenance record can be consulted using the full-function test kit or remotely via the communication network. It can be used as an aid in troubleshooting and to assist scheduling for device maintenance operations.

Recorded indications include:

Highest current measured

Operation counter (both cumulative total and total since last reset)

Number of test kit connections

Number of trips in operating mode

Contact wear (MasterPact NW only)

Load shedding and reconnection parameters can be set according to the power or the current flowing through the circuit breaker. Load shedding is carried out by a remote computer via the communication network or by an M2C or M6C programmable contact.

The M2C (two contacts) and M6C (six contacts) programmable contacts may be used to signal threshold overruns or status changes. They can be programmed using the keypad on the MicroLogic P and H trip units or remotely using the communication network. These contacts are required to obtain data from the protective relay functions on Type P and Type H trip units.

an electronic trip unit

MicroLogic 5.0P and 6.0P Trip Unit Settings

Micrologic 6.0p trip unit ground-fault setting, settings for alarms for other protection functions for micrologic 5.0p and 6.0p trip units, load-shedding settings for current and power metering for micrologic 5.0p and 6.0p trip units.

The last ten trips and ten alarms are recorded in two separate history files that can be displayed on the screen (sample displays are shown to the right). The following information is contained in these files:

The MicroLogic P trip unit calculates in real time all electrical values V, A, W, VAR, VA, Wh, VARh, VAh, Hz, power factor, and crest factor. The MicroLogic P trip unit also calculates demand current and demand power over an adjustable time period.

Real-Time Metering: The value displayed on the screen is refreshed every second. Minimum and maximum measurement values are stored in memory.

Demand Metering: The demand is calculated over a fixed or sliding time window that can be programmed from five to sixty minutes. Depending on the contract signed with the power supplier, specific programming makes it possible to avoid or minimize the cost of overrunning the subscribed power. Maximum demand values are systematically stored and time stamped.

Four wire Modbus, RTU, RS485—The communication network may be used to:

Remotely read parameters for the protection functions.

Transmit all the measurements and calculated values.

Signal the causes of tripping and alarms.

Consult the history files and the maintenance indicator record.

In addition, an event log of the last 100 events and a maintenance record, which is stored in the trip unit memory but not available locally, may be accessed via the communication network.

The Modbus communication system is compatible with Powerlogic™ System Manager™ (SMS) software.

The event log may be accessed by a remote computer via the communication network. All events are time stamped and include:

Beginning and end of alarms

Modifications to settings and parameters

Loss of time

Overrun of wear indicators

Test kit connections

Counter resets

System faults (thermal self-protection, major fault and minor fault alarms)

MicroLogic 5.0H and 6.0H Trip Units with Harmonic Metering

In addition to the P functions, the MicroLogic H trip units offer:

In-depth analysis of power quality including calculation of harmonics and the fundamentals.

Diagnostics aid and event analysis through waveform capture.

Customized alarm programming to analyze and track down a disturbance on the ac power system.

Systematic time stamping of all events and creation of logs.

The MicroLogic H trip unit offers all the measurements carried out by the MicroLogic P trip unit, with the addition of phase-by-phase measurements of power and energy as well as calculation of:

Current and voltage total harmonic distortion (THD, thd).

Current, voltage and power fundamentals (50/60 Hz).

Harmonic components (amplitude and phase) up to the 31st current and voltage harmonic.

Real-Time Metering : The value displayed on the screen is refreshed every second. The table below shows what is measured in real-time metering.

Demand Metering : Similar to the MicroLogic P trip unit, demand values are calculated over a fixed or sliding time window that can be set from five to 60 minutes.

MicroLogic H trip units can capture and store current and voltage waveforms using digital sampling techniques similar to those used in oscilloscopes. Using the information available in the captured waveform, it is possible to determine the level of harmonics as well as the direction and amplitude of the flow of harmonic power.

Users of MicroLogic H trip units can record manually via the keypad the following waveforms:

The four currents: I a , I b , I c , and I N

The three phase-to-phase voltages: V ab , V bc , and V ca

Waveforms may be displayed on the graphic screen of MicroLogic H trip units or communicated over a networked system. The recording takes place over one cycle with a measurement range of 0 to 1.5 I N for current and 0 to 690 volts for voltage. The resolution is sixty-four points per cycle.

The instantaneous value of each measurement can be compared to user-set high and low thresholds. Overrun of a threshold generates an alarm. Programmable action can be linked to each alarm, including circuit breaker opening, activation of an M2C or M6C contact, recording of measurements in a log, etc.

Each event is recorded with:

The date, time, and name of the event.

The event characteristics.

Setting the display language: System messages can be displayed in six different languages:

English - US

English - UK

The desired language is selected via the keypad.

Protection functions: All current-based protection functions require no auxiliary source. Voltage-based protection functions are connected to ac power via a voltage measurement input built into the circuit breaker on the bottom side. (Optional external voltage measurement is available.)

Accuracy of measurements (including sensors):

Voltage (V) 1%

Current (A) 1.5% (higher accuracy [1%] may be achieved with special calibration on the current transformer [CT characterization option])

Frequency (Hz) 0.1 Hz

Power (W) and energy (Wh) 2.5%

The MicroLogic H trip unit uses a dedicated metering data chain separate from the protection data chain so that a greater number of data samples can be used for metering. This increases the number of samples taken per time period, which in turn gives the H trip unit a higher degree of metering accuracy.

Stored information: The fine setting adjustments, the last 100 events and the maintenance record remain in the trip unit memory even when power is lost.

Reset: An individual reset, via the keypad or remotely, will reset alarms, minimum and maximum data, peak values, counters and the indicators.

MicroLogic Trip Unit Functions

an electronic trip unit

The long-time pickup switch sets the maximum current level the circuit breaker will carry continuously. The maximum current level (I r ) is the long-time pickup setting multiplied by the sensor plug amperage (I n ). If the current exceeds this value for longer than the long-time delay time, the circuit breaker will trip.

The long-time delay switch sets the length of time that the circuit breaker will carry a sustained overload before tripping. Delay bands are labeled in seconds of overcurrent at six times the ampere rating. For maximum coordination, there are eight delay bands. Long-time delay is an “inverse time” characteristic in that the delay time decreases as the current increases.

The trip unit includes an alarm indicator  that will be lit continuously when the current is above 100% of the pickup setting.

Short-Time and Instantaneous Trip Functions

an electronic trip unit

The short-time pickup switch sets the short-circuit current level at which the circuit breaker will trip after the set short-time delay. The short-time current (I sd ) equals the short-time pickup setting multiplied by the long-time pickup (I r ).

The short-time delay switch sets the length of time the circuit breaker will carry a short circuit within the short-time pickup range. The delay (based on 10 times the ampere rating I r ) can be adjusted to four positions of I 2 t ramp operation (I 2 t ON) or five positions of fixed time delays (I 2 t OFF). I 2 t ON delay is an “inverse time” characteristic in that the delay time decreases as the current increases. Short-time delay for the 2.0 trip unit is fixed at a delay band of 20 to 80 ms.

The instantaneous pickup switch sets the short-circuit current level at which the circuit breaker will trip with no intentional time delay. The instantaneous current (I i ) is equal to the instantaneous pickup setting multiplied by the sensor plug amperage (I n ).

The instantaneous function will override the short-time function if the instantaneous pickup is adjusted at the same or lower setting than the short-time pickup. In trip units with both adjustable short-time and instantaneous trip functions, the adjustable instantaneous trip can be disabled by setting Instantaneous pickup to OFF.

an electronic trip unit

The ground-fault pickup switch sets the current level at which the circuit breaker will trip after the set ground-fault delay. Ground-fault pickup values (I g ) are based on circuit breaker sensor plug (I n ) only, not on the rating plug multiplier (I r ). Changing the rating plug multiplier has no effect on ground-fault pickup values.

The ground-fault delay switch sets the length of time the circuit breaker will carry ground-fault current which exceeds the ground-fault pickup level before tripping. The delay (based on the sensor plug amperage (I n ) can be adjusted to four positions of I 2 t ramp operation (I 2 t ON) or five positions of fixed time delays (I 2 t OFF). I 2 t ON delay is an “inverse time” characteristic in that the delay time decreases as the current increases.

Enerlin'X Communication Wiring System

The wiring system is designed for low-voltage power switchboards. Installation does not require special tools or training. The prefabricated wiring ensures both data transmission (Modbus protocol) and 24 Vdc power distribution for the communications modules on the MicroLogic trip units.

an electronic trip unit

The MasterPact can be integrated into Ethernet and Modbus communication environments.

There are four possible functional levels that can be combined.

The Modbus RS 485 (RTU protocol) system is an open bus on which communicating Modbus devices (MasterPact NW with Modbus COM, Power Meter PM700, PM800, PowerPact P/Rframe, etc.) are installed. All types of PLCs and microcomputers may be connected to the bus.

The Modbus communication parameters (address, baud rate, parity) are entered using the keypad on the MicroLogic A, P, or H trip unit. For a switch, it is necessary to use the Electrical Asset Manager or RSU (Remote Setting Utility) MicroLogic utility.

Number of Devices

The maximum number of devices that may be connected to the Modbus bus depends on the type of device (ComPact circuit breaker with Modbus COM, PM700, PM800, MasterPact circuit breaker, etc.), the baud rate (19200 is recommended), the volume of data exchanged and the desired response time. The RS 485 physical layer offers up to thirty-two connection points on the bus (one master, thirty-one slaves).

Length of Bus

The maximum recommended length for the Modbus bus is 3940 feet (1200 meters).

Bus Power Source

A 24 Vdc power supply is required (less than 20% ripple, insulation class II).

Ethernet is a data link and physical layer protocol defined by IEEE 802 10 and 100 Mbps specifications that connects computer or other Ethernet devices. Ethernet is an asynchronous Carrier Sense Multiple Access with Collision detection (referred as CSMA/CD) protocol. Carrier Sense means that the hosts can detect whether the medium (coaxial cable) is idle or busy.

Multiple Access means that multiple hosts can be connected to the common medium. Collision Detection means a host detects whether its transmission has collided with the transmission of another host (or hosts).

IFE Ethernet interface can be connected to a PC or a laptop over Ethernet. The maximum length of Ethernet cable is 325 feet (100 meters). IFE Ethernet interface + gateway provides a Modbus TCP/IP gateway over Ethernet to enable Modbus TCP communication from a Modbus TCP master to any Modbus slave devices connected to it. The maximum active Modbus TCP client connection is twelve.

IFE Ethernet interface has an embedded web server (web page).

All Masterpact devices can be fitted with the communication function thanks to the COM option. Masterpact uses the Ethernet or Modbus communications protocol for full compatibility with the supervision management systems.

For fixed and drawout devices, the common communication option is made up of:

BCM ULP Module

an electronic trip unit

A BCM ULP module, installed behind the MicroLogic trip unit and supplied with a set of switches (OF, SDE, PF and CH switches), a kit for connection to shunt close (XF) and shunt trip (MX1) communicating voltage releases, and a COM terminal block (inputs E1 to E6). This module is independent of the trip unit and receives and transmits information on the communication network. An infra-red link transmits data between the trip unit and the communication module. (Consumption: 30 mA, 24 V)

The IFM module, the Modbus interface for connection to the network, contains the Modbus address (1 to 99) declared by the user using the two dials in front. It automatically adapts (baud rate, parity) to the Modbus network in which it is installed.

The IFE module, the Ethernet interface for low-voltage circuit breakers, enables an intelligent modular unit (IMU) such as a Masterpact NT/NW or PowerPact circuit breaker to be connected to an Ethernet network. Each circuit breaker has its own IFE and a corresponding IP address.

For drawout devices the Cradle Management option must be added:

IO Application Module

an electronic trip unit

The IO (Input/Output) application module for low-voltage circuit breakers is delivered with the drawout devices ordered with the COM option for cradle management. It must be installed on a steel DIN rail that is properly grounded near the device. The IO module must be connected to the ULP system and to the cradle position contacts (CD, CT, CE) that transmit the position of the circuit breaker in the cradle.

For communicating remote control, shunt close (XF) and shunt trip (MX1) communicating voltage releases must be added:

The shunt close (XF) and shunt trip (MX1) communicating voltage releases are equipped for connection to the communication module.

The remote-tripping function shunt trip (MX2) and undervoltage release (MN) are independent of the communication option. They are not equipped for connection to the communication module.

Communication Architecture–Electrically Operated

an electronic trip unit

IFE Ethernet Interface

IFE Interface

an electronic trip unit

The IFE interface and IFE interface + gateway enable low-voltage circuit breakers such as MasterPact NT/NW or PowerPact P/R-frame to be connected to an Ethernet network.

Provides Ethernet access to a single low-voltage circuit breaker.

Function: Interface - one circuit breaker is connected to the IFE interface using its ULP port.

IFE Interface + Gateway

Provides Ethernet access to one or several low-voltage circuit breakers.

Interface - one circuit breaker is connected to the IFE interface using its ULP port.

Gateway: several circuit breakers on a Modbus network are connected using the IFE interface + gateway master Modbus port.

an electronic trip unit

IFE Interface, IFE Interface + Gateway Features

Dual 10/100 Mbps Ethernet port for simple daisy chain connection.

Device profile web service for discovery of the IFE interface, IFE interface + gateway on the LAN.

Ethernet interface for MasterPact and PowerPact circuit breakers.

Gateway for Modbus-SL connected devices (IFE interface + gateway only).

Embedded set-up web pages.

Embedded monitoring web pages.

Embedded control web pages.

Built-in e-mail alarm notification.

IFE Interface, IFE Interface + Gateway Screen

an electronic trip unit

The IFE interface and IFE interface + gateway are DIN rail mounted devices. A stacking accessory enables the user to connect several IFMs (ULP to Modbus interfaces) to an IFE interface + gateway without additional wiring.

The IFE interface and the IFE interface + gateway must always be supplied with 24 Vdc.

The IFMs stacked to an IFE interface + gateway have power supplied by the IFE interface + gateway, thus it is not necessary to supply them separately. It is recommended to use a UL listed and recognized limited voltage/limited current or a class 2 power supply with a 24 Vdc, 3 A maximum.

The connection to an IFE interface or IFE interface + gateway requires a communication module embedded into the circuit breaker:

MasterPact NT/NW (fixed or drawout) circuit breakers: BCM ULP communication module

Drawout MasterPact NT/NW circuit breakers: BCM ULP and its respective IO (Input/Output) application module.

All connection configurations for MasterPact NT/NW circuit breakers require the circuit breaker ULP cord. The insulated NSX cord is mandatory for system voltages greater than 480 Vac. When the second ULP RJ45 connector is not used, it must be closed with a ULP terminator (TRV00880).

Network Communication Interface

Ifm modbus communication interface.

IFM Modbus Communication Interface. Ref.: TRV00210

an electronic trip unit

An IFM Modbus communication interface is required for connection of a MasterPact or PowerPact circuit breaker to a Modbus network as long as this circuit breaker is provided with a ULP (Universal Logic Plug) port. The port is available on the BCM ULP.

Once connected, the circuit breaker is considered as a slave by the Modbus master. Its electrical values, alarm status, open/close signals can be monitored or controlled by a Programmable Logic Controller or any other system.

Two RJ45 sockets, internal parallel wiring.

Connection of a single circuit breaker.

A ULP line terminator or an FDM121 display unit must be connected to the second RJ45 ULP socket.

The RJ45 sockets deliver a 24 Vdc supply fed from the Modbus socket.

Built-in test function, for checking the correct connection to the circuit breaker and FDM121 display unit.

Modbus Slave Port

Top socket for screw-clamp connector, providing terminals for:

— 24 Vdc input supply (0 V, +24 V)

— Modbus line (D1, D2, Gnd) 2-wire Modbus system

Lateral socket, for DIN-rail stackable connector. Both top and lateral sockets are internally parallel wired.

Multiple IFMs can be stacked, thus sharing a common power supply and Modbus line without individual wiring.

On the front face:

— Modbus address setting (1 to 99): two coded rotary switches

— Modbus locking pad: enables or disable the circuit breaker remote control and modification of IFM parameters

Self-adjusting communication format (Baud rate, parity).

Stacking an IFM

The IO (Input/Output) application module for an low-voltage circuit breaker is part of an ULP system with built-in functions and applications to enhance the application needs. The ULP system architecture can be built without any restrictions using the wide range of circuit breakers.

The IO application module is compliant with the ULP system specifications.

Two IO application modules can be connected in the same ULP network.

The ranges of low-voltage circuit breakers enhanced by the IO application module are:

MasterPact NW

MasterPact NT

PowerPact R-Frame

PowerPact P-Frame

The IO application module resources are:

Six digital inputs that are self powered for either NO and NC dry contact or pulse counter.

Three digital outputs that are a bistable relay (5 A maximum).

One analog input for PT100 temperature sensor.

The pre-defined application adds new functions to the IO application module by:

Selection by the application rotary switch on the IO application module, defining the application with pre-defined input/output assignment and wiring diagram.

No additional setting with the customer engineering tool required.

The resources not assigned to the pre-defined application are free for additional user-defined applications:

cradle management

circuit breaker operation

cradle management + ERMS (Energy Reduction Maintenance Setting)

light and load control

User-defined applications are processed by the IO application module in addition to the pre-defined application selected.

The user-defined applications are available depending on:

the pre-defined application selected

the IO application module resources (inputs and outputs) not used by the application

The resources required by user-defined applications are assigned using the customer engineering tool:

energy management

The IO application module is a DIN rail mounted device. Install on a steel DIN rail that is properly grounded near the device.

The application rotary switch enables the selection of the pre-defined application. It has nine positions and each position is assigned to a pre-defined application. The factory set position of the switch is pre-defined application one.

The setting locking pad on the front panel of the IO application module enables the setting of the IO application module by the customer engineering tool.

Electrical Asset Manager Configuration Engineering Tool (EcoStruxure ™ Power Commission)

The EcoStruxure Power Commission engineering tool is a software application that helps the user to manage a project as part of designing, testing, site commissioning, and maintenance of the project life cycle. It enables the user to prepare the settings of the devices offline (without connecting to the device) and configure them when connected with the devices. It also provides other value-added features for the user to manage the project such as: safe repository in cloud, attach artifacts to each device or at the project level, organize devices in switchboard, manage a hierarchical structure of the installation, etc.

an electronic trip unit

The EcoStruxure Power Commission software is compatible with the following devices:

ComPact NSX100-630 (IEC) circuit breakers

PowerPact (UL) circuit breakers

ComPact NS630b-3200 (IEC) circuit breakers

MasterPact NT/NW (IEC and UL) circuit breakers

Compatible devices (Device Management in the project)

Switches (ComPact NSX, MasterPact & PowerPact Family)

Third party devices

References:

The EcoStruxure Power Commission software package can be downloaded from our website:

The EcoStruxure Power Commission Software includes the Schneider Electric customer engineering tools such as the Remote Setting Utility (RSU) and Remote Control Utility (RCU) with additional features.

The EcoStruxure Power Commission Software supports the connection of Schneider Electric communicable devices to:

create projects by device discovery, selection of devices, and importing a Bill of Material (BOM)

monitor the status of protection and IO status

read information (alarms, measurements, parameters)

check protection discrimination between two devices

upload and download of configuration or settings in batch mode to multiple devices.

carry out commands and tests

generate and print a device settings report and communication test report

manage multiple devices with a electrical and communication hierarchy model

manage artifacts (project documents)

check consistency in settings between devices on a communication network

compare configuration settings between PC and device (online)

download latest firmware

The EcoStruxure Power Commission Software enables the user to access the advanced features of the software once the project is saved in the Schneider Electric cloud.

Show QR code for this page

QR Code is a registered trademark of DENSO WAVE INCORPORATED in Japan and other countries.

Was this helpful?

Contact Information

Legal information.

The information provided in this document contains general descriptions, technical characteristics and/or recommendations related to products/solutions.

This document is not intended as a substitute for a detailed study or operational and site-specific development or schematic plan. It is not to be used for determining suitability or reliability of the products/solutions for specific user applications. It is the duty of any such user to perform or have any professional expert of its choice (integrator, specifier or the like) perform the appropriate and comprehensive risk analysis, evaluation and testing of the products/solutions with respect to the relevant specific application or use thereof.

The Schneider Electric brand and any trademarks of Schneider Electric SE and its subsidiaries referred to in this document are the property of Schneider Electric SE or its subsidiaries. All other brands may be trademarks of their respective owner.

This document and its content are protected under applicable copyright laws and provided for informative use only. No part of this document may be reproduced or transmitted in any form or by any means (electronic, mechanical, photocopying, recording, or otherwise), for any purpose, without the prior written permission of Schneider Electric.

Schneider Electric does not grant any right or license for commercial use of the document or its content, except for a non-exclusive and personal license to consult it on an "as is" basis.

Schneider Electric reserves the right to make changes or updates with respect to or in the content of this document or the format thereof, at any time without notice.

To the extent permitted by applicable law, no responsibility or liability is assumed by Schneider Electric and its subsidiaries for any errors or omissions in the informational content of this document, as well as any non-intended use or misuse of the content thereof.

© 2000 – 2019 Schneider Electric

  • Get custom product tools and services
  • Access training
  • Manage support cases
  • Create and manage your orders (authorized partners only)

Welcome to the Schneider Electric Website

Search FAQs

What are thermal-magnetic or electronic trip unit, released for: schneider electric thailand.

an electronic trip unit

Articles that might be helpful

Discuss this topic with experts

Start here!

Find answers now. Search for a solution on your own, or connect with one of our experts.

Contact Support

Reach out to our customer care team to receive more information, technical support, assistance with complaints and more.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Search topic-related frequently asked questions to find answers you need.

Contact Sales

Start your sales inquiry online and an expert will connect with you.

IMAGES

  1. Circuit breaker electronic trip unit explained

    an electronic trip unit

  2. The Electronic Trip Unit is a microprocessor controlled, multifunction

    an electronic trip unit

  3. LT360032 Eaton 310 LSI Electronic Trip Unit 600A

    an electronic trip unit

  4. LV429075

    an electronic trip unit

  5. Electronic Trip Circuit Breaker Basics: Schneider Electric Micrologic

    an electronic trip unit

  6. Micrologic 4 Electronic Trip Units

    an electronic trip unit

VIDEO

  1. Assemble of Siemens 3WT9841-5AB00 ETU37WT Electronic Trip Unit ETU of 3WT ACB

  2. electronic trip unit how it work

  3. Design of Digital Circuits

  4. Port electric

  5. Assemble of Siemens 3WT9841-5AB00 ETU37WT Electronic Trip Unit ETU to 3WT ACB 2000A 4-POLE SIZE

  6. MCCB breaker Advanced मूविंग और फिक्स कांटेक्ट कैसे काम करते हैं। 🤔😊

COMMENTS

  1. The Basics Of Circuit Breaker Tripping Units - EEP

    The electronic trip units instead use a microprocessor to process the current signal and operate the circuit breaker opening in case of fault. In addition to this, electronic tripping units offer more tripping criteria which are not feasible with electromechanical releases.

  2. MicroLogic ™ Electronic Trip Systems - Schneider Electric

    The MicroLogic P trip unit calculates in real time all electrical values V, A, W, VAR, VA, Wh, VARh, VAh, Hz, power factor, and crest factor. The MicroLogic P trip unit also calculates demand current and demand power over an adjustable time period.

  3. Circuit breaker electronic trip unit explained - YouTube

    The Electronic Trip Unit is a microprocessor controlled, multi-function over-current protective device for application with low voltage power circuit breakers. The adjustment flexibility...

  4. Micrologic Trip Units | Schneider Electric USA

    All Micrologic trip units provide impeccable, electronic circuit protection with adjustable protection settings for maximum system coordination and flexibility. Sophisticated functionality, such as energy and power quality metering capabilities, is integrated in the more advanced trip units.

  5. MicroLogic 5 and 6 Electronic Trip Units User Guide for ...

    MicroLogic 5 and 6 Electronic Trip Units User Guide for PowerPacT H-, J-, and L-Frame Circuit Breakers. This manual describes operation of the MicroLogic 5 and 6 trip units for PowerPacT H-, J-, and L-Frame Circuit Breakers. Date: June 26 2024| Type: User guide.

  6. What are Thermal-magnetic or electronic trip unit ...

    Thanks to digital electronics, trip units have become faster as well as more accurate and reliable. Wide setting ranges make installation upgrades easier. Designed with processing capabilities, Micrologic trip units can provide measurement information and device operating assistance.